Home Categories Send inquiry

Hot Sale for Biomass Steam Boiler - Vertical Wood /Coal Boiler – Double Rings

Introduction :

Vertical type boiler, adopt water&fire tube structure, suitable for coal/wood/solid material fire.
Vertical boiler, thermal capacity in 100kw/200kw/300kw/350kw/500kw/600kw/700kw/1000kw per hour.

Feature:

* Compact, small footprint, easy installation.
* Fully furnished heating surface, flue gas temperature is low.
* Using the world famous original burner, implement automatic and efficient combustion, the combustion efficiency.
* Microcomputer automatic control, super-pressure automatic protection, low water level automatic protection and automatic replenishment.
* Extra-thick insulation layer design, effective insulation, furnace surface testimonies low heat loss.
* The concentration of dust emission is small, fully meet the state requirements for a class of environmental protection areas.

Parameter :

Main Specification :

Model

LSC0.3-0.7-AⅡ

LSC0.5-0.7-AⅡ

LSC0.7-0.7-AⅡ

LSC0.95-0.8-AⅡ

Steam Capacity t/h

0.3

0.5

0.7

0.95

Steam Pressure MPa

0.7

0.8

Temperature ℃

170.4

175.35

Running Range in the safety  %

80-100

 Fuel

 Bituminous Coal

Fuel Consumption Kg/h

56.1

92.8

129.1

177.2

Efficiency %

78

78.8

79.45

78.7

Exhaust Gas Temperature ℃

201.7

203.8

193.3

200.2

Exhaust Gas Ratio

1.5

1.4

1.35

1.45

Feed Water Temperature℃

20

Boiler Body Cost Weight

1.847

2.876

3.431

4.876

Steel Frame Weight

1.3

1.57

1.71

1.9

Chain Weight

76

110

127

260

Power KW

3

3

3

3

Water Quality

Water Hardness:≤0.03  Oxygen Capacity:≤0.1mg/L

Boiler water alkalinity 10.0-12.0PH(25℃)

Blowdown Rate %

2

Boiler design, manufacture, operation main implementation criteria:
1、"Steam Boiler Safety Technology Supervision" 96 edition
2、"Supervision and management regulations for energy saving technologies" TSGG0002-2010
3、GB/T16508-1996 "Shell boiler pressure parts strength calculation"
4、"Laminar burning industrial boilers burning and boiling thermal calculation method"
5、"Boiler equipment aerodynamic calculation standard method"
6、"Boiler installation construction and acceptance norms" GB50273-2009
7、"Industrial Boiler Water Quality "GB/T1576-2008

  • Hot Sale for Biomass Steam Boiler - Vertical Wood /Coal Boiler – Double Rings Related Video: